DEGSON DSPT Series Power Surge Protective Devices: Which Scenarios Do They Apply To?
Description: The DEGSON DSPT series power surge protective devices cover T1/T2/T3 three-level protection, with a maximum discharge capacity of 100 kA (10/350 μs). They feature low residual voltage, no follow current, hot-swappable modules, and remote signaling alarms, making them suitable for power surge protection in industrial automation, data centers, wind and solar power, elevators, rail transit, and other scenarios. This article provides a comprehensive analysis covering product definition, functions, features, application cases, and selection guidelines.
Keywords: DEGSON, DSPT, surge protective device, SPD, power lightning protection, T1/T2/T3, industrial automation, low residual voltage, hot-swappable
1. What Is It?
The DEGSON DSPT series power surge protective devices (SPD) are transient overvoltage protection devices developed by DEGSON for low-voltage power distribution systems. They are installed in parallel at the power incoming end to divert transient high currents caused by lightning induction and switching overvoltages, clamping the line voltage within a range that downstream equipment can withstand.
Based on protection class (IEC 61643-11), the DSPT power product line is divided into three sub-series:
| Sub-series | Protection Class | Typical Waveform | Installation Location |
|---|---|---|---|
| DSPT-T1/T2 | Class I (T1+T2 combined) | 10/350 μs + 8/20 μs | Incoming line of main distribution cabinet; withstands direct lightning current |
| DSPT-T2 | Class II (T2) | 8/20 μs | Floor/workshop sub-distribution box; absorbs residual surges |
| DSPT-T3 | Class III (T3) | Combined wave | End of precision equipment; fine protection |
The three levels can be used independently, or linked as a three-level protection system — "main input → sub-distribution → end devices" — to form a complete power lightning protection architecture.
2. What Does It Do?
A surge is a transient overvoltage pulse with a steep rising edge that exceeds the normal operating voltage. There are two main sources:
1. Natural sources: Direct lightning strikes, induced lightning intruding along power lines, and ground potential rise;
2. Man-made sources: Start/stop of heavy equipment, short-circuit faults, power source switching, and switching overvoltages from reactive power compensation.
The damage caused is often not "instant failure" but gradual degradation:
1. Accelerated aging: Repeated surges reduce the insulation life of semiconductor devices, causing premature failure;
2. Direct damage: A single strong surge can puncture the power modules of PLCs, VFDs, and servo drives;
3. Interference and downtime: Surges cause control system malfunctions and communication packet loss, leading to unplanned production line downtime;
4. Safety risks: In continuous-process industries such as chemical and energy, unexpected downtime can trigger secondary incidents.
The core function of the DSPT series is to divert surges to ground and clamp the residual voltage to a low level before they reach sensitive equipment — essentially a "safety valve" for the power circuit.
3. Key Features
1. High discharge capacity, low residual voltage
The power product line offers a maximum discharge capacity of 100 kA (10/350 μs), capable of withstanding Class I direct lightning strikes. The no-follow-current design prevents power-frequency follow current after operation, and combined with low residual voltage, provides more thorough protection for downstream equipment.
2. Full system compatibility, multiple voltage ratings
Supports mainstream power distribution systems worldwide (TT, TN-S, TN-C-S, IT, etc.), with AC voltage ratings covering 275 V / 320 V / 385 V / 420 V / 690 V, adapting to single-phase 220 V, three-phase 380 V, and industrial 690 V systems.
3. Three-level status indication
1. Visual indication: Module window — green = normal, red = failed, replace required;
2. Remote signaling: Dry contact output that connects to PLC/SCADA for remote status monitoring;
3. Automatic disconnection: When a module degrades to the critical threshold, the thermal disconnector automatically disengages it from the grid to prevent short circuits and fire.
4. Pluggable and easy to maintain
The base-and-pluggable-module structure supports online hot-swapping — modules can be replaced without powering down or rewiring, minimizing downtime. Standard 35 mm DIN-rail mounting with a compact footprint fits conventional distribution cabinet depths.
5. Wide-temperature reliability
Operating temperature range of −40 °C to +80 °C, with a UL 94 V-0 flame-retardant housing, suitable for outdoor cabinets and harsh conditions such as extreme cold and high heat.
4. Application Cases
Case 1: Lithium battery production line — PLC control cabinet power protection
In a power battery plant, a DSPT-T2 (385 V, In = 20 kA) was installed at the incoming end of the coating machine control cabinet. Located in a lightning-prone area, the plant had suffered repeated PLC power module failures during the rainy season. After installation, combined with the DSPT-MCR series on the signal side, surge-related downtime dropped to zero for the entire year.
Case 2: Data center — three-level coordinated protection
1. Main electrical room: DSPT-T1/T2 (Imax = 100 kA) diverts direct lightning current;
2. UPS input cabinet: DSPT-T2 (Up ≤ 1.5 kV) absorbs residual surges;
3. Front of rack PDU: DSPT-T3 provides fine protection for server power. The three levels work together to keep the residual voltage reaching IT equipment below 1 kV, meeting the data center lightning protection requirements of GB 50343.
Case 3: Wind turbine tower — 690 V system protection
Wind turbines are located on open high ground with high lightning strike probability, and the converter system operates at 690 V. A DSPT-T2 (Uc = 690 V) was installed in the tower base control cabinet. Its −40°C cold-start capability suits northern winter conditions, and the hot-swappable module simplifies maintenance at height.
Case 4: Smart elevator — machine room and hoistway power distribution
Elevator VFDs and door controllers in the control cabinet are sensitive to overvoltage. A DSPT-T2 was installed in the machine room distribution box and a DSPT-T3 at the front end of the car control board, resolving the recurring issue of elevators frequently reporting fault codes and requiring resets during lightning season.
Case 5: PV inverter — AC and DC side protection
Induced lightning risk is high on the PV array side. A DSPT-T2 (Type 2) was configured at the inverter's AC output, combined with a DC-side SPD, protecting the inverter's IGBT modules from surge puncture.
5. Summary
The DEGSON DSPT series power surge protective devices are built around a complete T1/T2/T3 three-level product line, covering full-chain protection from the main incoming line to end devices. Features such as 100 kA high discharge capacity, low residual voltage, no follow current, hot-swapping, and remote signaling make them suitable for scenarios demanding high power supply continuity, including industrial automation, power distribution, data centers, new energy, rail transit, elevators, and security systems.
Three key points for selection:
1. Choose the level by location: T1/T2 for main input, T2 for sub-distribution, T3 for end precision equipment;
2. Choose Uc by system: Uc must be higher than the system's maximum continuous operating voltage;
3. Choose Up by equipment: Up must be lower than the protected equipment's impulse withstand voltage.
Properly configuring the DSPT series keeps surge risks away from equipment at a relatively low cost — a fundamental step in ensuring continuous production line operation.
6. FAQ (6 Common Questions)
Q1: What is the difference between DSPT-T1/T2 and DSPT-T2, and how should I choose?
A: The T1/T2 is a combined type that withstands both the 10/350 μs direct lightning waveform (Class I test) and the 8/20 μs induced lightning waveform (Class II test), with higher discharge capacity, and is used at the building main incoming line. The T2 only passes the Class II test and is used for sub-distribution boxes or floor boxes. In short: choose T1/T2 at the incoming end and T2 downstream.
Q2: Do surge protective devices require regular replacement?
A: Under normal conditions, no regular replacement is needed. However, after every strong lightning strike, check the module window color. Green means normal; red means the module has degraded and disconnected, requiring immediate replacement with the same model. An annual visual and remote signaling inspection before the rainy/lightning season is recommended.
Q3: Is a lower Up (voltage protection level) always better?
A: Given sufficient discharge capacity and Uc, a lower Up provides better protection for downstream equipment. However, an extremely low Up usually means limited discharge capacity. The selection principle is: Up must be lower than the protected equipment's impulse withstand voltage (typically 80% of the equipment's withstand rating), while balancing discharge capacity accordingly.
Q4: Can DSPT devices be connected in parallel?
A: Paralleling for higher discharge capacity is not recommended. When identical modules are paralleled, differences in response time cause uneven current sharing, which may damage one module first. For higher capacity needs, choose a higher-rated model directly (e.g., upgrade from T2 to T1/T2 combined type).
Q5: What are the grounding requirements for installation?
A: The grounding conductor should be as short and thick as possible — length no more than 0.5 m, cross-section no less than 16 mm² (T1/T2 level) or 10 mm² (T2 level) — and should be connected to the nearest equipotential bonding bar. Long conductors add inductance that raises the actual residual voltage and weakens protection.
Q6: After installing DSPT, can equipment still be damaged by lightning?
A: The DSPT protects against conducted surges intruding along the power line. If equipment also has signal lines, antennas, or outdoor cables, corresponding signal-type SPDs (e.g., DSPT-MCR, DSPT-CAT) must be added to those circuits. In addition, external lightning protection (air terminals, down conductors, grounding grid) and equipotential bonding must be in place. Only with a complete system of "external protection + internal protection + equipotential bonding" can lightning damage risk be minimized.